Overview
CEA-100 combustion efficiency analyser continuously detects the contents of carbon monoxide (CO) and oxygen (O2) in flue gas based on duplicate sensor technology. It provides an accurate, reliable and economical solution for boiler efficiency measurement. Designed for ease of maintenance and packaged for the industrial environment, CEA-100 is simple to install.
Product Features
CO combustion zone breaks traditional technology, innovative ideas, ease of use, not affected by factors such as loading, coal etc
The analyzing system is not affected by flue air leakage , less measurement error It is easy to achieve minimum heat loss and maximum combustion efficiency
Adjust air volume through analyzing concentration of CO and O2, a new strategy to control combustion
Preventing high temperature corrosion on water wall tubes
Typical Applications
Boilers Incinerator Klin
Measuring Range |
1 ~ 4000ppm |
Accuracy |
± 1.0% |
Resolution Ratio (Optional) |
1ppm (1mg) |
Response time |
T90 < 30S |
Repeatability |
± 1.0% |
||
Linear |
< 2% R |
||
Zero-drift/Span-drift |
Max 20ppm / < 2% R / Month |
||
Current Loop Outputs |
4mA ~ 20mA isolated Output, Maximum Loop Impdance 1000 Ω |
||
Operating Temperature |
-40 ~ +75�C (-40 ~ + 167�F) |
||
EMC |
EN-61326 |
||
Power Supply |
EN-61010-2,220V 50Hz,300W |
||
Zero Calibration (Air) |
4 ~ 8 bar, Clean & Dry, Flow Volume 6L/min |
||
Cooling Air |
4 ~ 8 bar, Clean & Dry, Flow Volume 90L/min, Ambient temperature<30oC, cooling is not required |
||
Overall Dimension |
950mm x 650mm x 230mm |
||
Weight |
60kg |
||
Standard Gas Categories |
Target gas CO; Background gas N2 |